How do you calculate attic ventilation per code?

Short answer. Per the International Residential Code, calculate attic ventilation by dividing the attic floor area by 150 to get the minimum net free area; you may divide by 300 instead only if 40 to 50 percent of that area is in upper vents no more than 3 feet below the ridge, with the rest in the lower part of the attic. Then confirm the vents are screened, installed per the manufacturer, and not blocked by insulation.

Step 1: decide which ratio you may use

Step 2: run the numbers

Example: a 1,600 square foot attic with a ridge vent and soffits.

If the exhaust were box vents placed halfway down the slope, they would not count as upper vents, and the attic would need 1,536 square inches at 1/150.

Step 3: check the other code items

Step 4: confirm the local edition

Georgia's residential code is based on the IRC with state amendments, and local building departments enforce the edition currently adopted. Check with yours if a permit is involved. See roofing permits in Georgia and roof ventilation basics.

In depth

Does a hot Georgia attic shorten the life of your shingles?How hot Georgia attics and shingles get, what research says about ventilation and shingle life, and when radiaHow much attic ventilation does a Georgia roof need?Attic ventilation for Georgia homes: intake and exhaust balance, the IRC R806 1/150 and 1/300 rules with workeRidge vent or box vents: which is better, and can you use both?Ridge vents vs box vents, turbines and power fans for Georgia attics: how each works, why mixing exhaust types