Is attic ventilation required, and how do you calculate how much is required?
Who requires it
Three parties care about your attic vents. The building code sets the minimum for new construction and permitted work. The shingle manufacturer usually ties its limited warranty to code compliant ventilation. And home inspectors flag missing or blocked vents during a sale. Georgia's current mandatory residential code is the 2024 International Residential Code with Georgia amendments, effective January 1, 2026, enforced by your city or county building department.
The calculation, step by step
- Measure the attic floor area. Example: a 40 by 50 foot attic is 2,000 square feet.
- Divide by 300 if the vents will be balanced high and low, or by 150 if they cannot be. 2,000 divided by 300 is about 6.7 square feet.
- Multiply by 144 to convert to square inches: about 960 square inches of net free area.
- Split it. Code allows 40 to 50 percent up high, so roughly 480 square inches of exhaust and 480 of intake. Many roofers aim for slightly more intake than exhaust.
- Divide each half by the net free area printed on the vent or its packaging to get feet of ridge vent or the number of soffit vents.
Details that trip people up
The high vents must sit within 3 feet of the ridge, measured vertically, to qualify for the 1/300 ratio. Vent openings need screening with openings between 1/16 and 1/4 inch. Insulation must not block the eave vents, and there must be at least 1 inch of air space under the deck at those vents. For a refresher on how the pieces fit, read roof ventilation basics, and see roofing permits in Georgia for how local enforcement works.